Toshiba 1600XP Power Supply User Manual


 
52
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
503 Discharge Cur-
rent
Battery Discharge Current
- UPS calculates and shows discharged current
during Backup and 0.0 Vdc for others modes
of UPS
Monitor BATT 22.0 Vdc Nonchangeable
Nonchangeable
User
Administrator
506 Charger Status Battery Charger Status
- Shows charger’s status which can be Normal,
Preventive and Stop
Monitor BATT Normal Nonchangeable
Nonchangeable
User
Administrator
507 Total Discharg-
es
Number of Battery Discharges
- Increment count by one after UPS in Backup
mode for 10 seconds
Settings BATT 123 Nonchangeable
Nonchangeable
508 Cal Battery Vsd Calculated Battery Shutdown Voltage
- Calculated from the discharge rate during
Backup mode
Monitor BATT 172 Vdc Nonchangeable
Nonchangeable
User
Administrator
509 Batt Life Re-
main
Battery Lifetime Remaining Settings BATT 43800 Hr Nonchangeable
Nonchangeable
User
Administrator
511 Rated Ahr* Rated Battery Ampere Hour
- One of the battery’s properties
Settings BATT 9 AHr Nonchangeable
Nonchangeable
User
Administrator
512 No
Batt(Series)*
Number of Battery in Series Settings BATT 18 Nonchangeable
Nonchangeable
User
Administrator
513 No Batt(Paral)* Number of Battery in Parallel Settings BATT 1 Nonchangeable
Nonchangeable
User
Administrator
514 Batt Ins Date Battery installation Date
- YYYY/MM/DD format
Settings BATT 2008/01/01 Nonchangeable
Nonchangeable
User
Administrator
516 Batt SDown
Level*
Battery Shutdown Level
- Percentage setting for shutdown level calcu-
lated. Actual shutdown level might be different
depends on the rate of discharge
Settings BATT 79 % Nonchangeable
Nonchangeable
User
Administrator
524 SbatEx External Battery Status Settings BATT Disable Nonchangeable
Nonchangeable
User
Administrator
525 Ex # Batt
(Series)
Number of External Battery in Series Settings BATT 18 Nonchangeable
Nonchangeable
User
Administrator
526 Ex # Batt
(Parallel)
Number of External Battery in Parallel Settings BATT 1 Nonchangeable
Nonchangeable
User
Administrator
527 Ex Batt Rated
Ahr
External battery’s Rated Ampere-Hour capacity Settings BATT 9 AHr Nonchangeable
Nonchangeable
User