Toshiba 1600XP Power Supply User Manual


 
69
1600XP Series Installation and Operation Manual
Parts Replacement
The following list shows recommended intervals for periodic replacement of certain UPS parts:
Aluminum electrolytic 1. capacitors: Replace once every 5 years.
Fuses: Replace once every 7 years.2.
3. Cooling fan: When operated in an ambient temperature of 86 °F (30 °C) to 104 °F (40°
C), replace every 3.5 years. When operated in an ambient temperature of less than 86 °F
(30 °C) , replace every 5 years.
NOTE: The cooling fans are not hot swappable. Remove all power from the UPS before
replacing the cooling fans.
(Open the UPS main circuit breaker, disconnect external battery cabinets, and partially slide
out the top battery trays enough to open the internal DC power circuit.)`
Batteries: In order to maintain system reliability, the UPS batteries should be replaced on a 4.
regular schedule. To ensure reliable operation, all of the batteries should be replaced at the
same time. Use the following chart for replacement:
UPS BATTERY REPLACEMENT
BATT AMB TEMP* AVERAGE LIFETIME
68 – 77 °F (20 – 25 °C) Approximately 5 yrs.
86 °F (30 °C) Approximately 3.5 yrs.
95 °F (35 °C) Approximately 2.5 yrs.
104 °F (40 °C) Approximately 1.8 yrs.
113 °F (45 °C) Approximately 1.25 yrs.
* Continual operation at ambient temperatures above 25 °C will degrade the battery life.
Optional Receptacle Panel Installation Instructions
These are the instructions for installing the optional Modular Output Receptacle Panels for the 1600XP
Series UPS. These instructions apply to all UH3-RP-XX panel options.
WARNING: The work outlined in these instructions is to be performed only on a completely un-energized
UPS system.