Toshiba 1600XP Power Supply User Manual


 
51
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
303 Bypass Voltage Bypass Voltage
- Present calculated bypass voltage
Monitor BYP 240 V Nonchangeable
Nonchangeable
User
Administrator
304 Bypass Current Bypass Current
- UPS presently calculated bypass current
Monitor BYP 25.0 A Nonchangeable
Nonchangeable
User
Administrator
305 Bypass Fre-
quency
Bypass Frequency
- UPS presently calculated bypass frequency
Monitor BYP 60.0 Hz Nonchangeable
Nonchangeable
User
Administrator
307 Bypass
Power(VA)
Bypass Apparent Power
- UPS presently calculated bypass apparent
power.
Monitor BYP 6000 VA Nonchangeable
Nonchangeable
User
Administrator
315 VBypUV De-
Level*
Bypass Undervoltage Detection Level - Per-
centage of rated input voltage command ID
111.
Setting BYP 62 % Nonchangeable
Nonchangeable
User
Administrator
316 VBypUV
ReLevel*
Bypass Undervoltage Recovery Level in per-
centage
- Of rated input voltage command ID 111.
Setting BYP 66 % Nonchangeable
Nonchangeable
User
Administrator
317 VBypOV De-
Level
Bypass Over Voltage Detection Level in Volt Setting BYP 284 V Nonchangeable
Nonchangeable
User
Administrator
318 VBypOV
ReLevel
Bypass Over Voltage Recovery Level in Volt Setting BYP 274 V Nonchangeable
Nonchangeable
User
Administrator
401 DC Bus Total DC Bus Voltage Total
- Currently calculated DC Bus total voltage
Monitor DC 770 Vdc Nonchangeable
Nonchangeable
User
Administrator
402 DC Bus Posi-
tive
DC Bus Voltage (+)
- UPS presently calculated DC Bus positive
voltage
Monitor DC 385 Vdc Nonchangeable
Nonchangeable
User
Administrator
403 DC Bus Nega-
tive
DC Bus Voltage (-)
- UPS presently calculated DC Bus negative
voltage
Monitor DC 385 Vdc Nonchangeable
Nonchangeable
User
Administrator
404 Rated DC Bus* Rated DC Bus Voltage
- Used to calculated percentage.
Setting DC 770 Vdc Nonchangeable
Nonchangeable
User
Administrator
501 Battery Voltage Charger or Battery Voltage
- UPS calculates and shows current charger
voltage during charging or battery voltage dur-
ing Backup
Monitor BATT 234 Vdc Nonchangeable
Nonchangeable
User
Administrator