Toshiba 1600XP Power Supply User Manual


 
42
1600XP Series Installation and Operation Manual
Screen Tab: Settings
The tables on pages 47 – 51 list the 1600XP Settings parameters that can be viewed in the MONITOR
tab.
Example: The Settings parameter Batt Test Freq (Battery Test Frequency) can be viewed by USR (User)
level and above, only logged in ADM (Administrators) and above can edit the value.
Each key displays a block of relevant command parameters:
Key – (Cmd ID range) Types of Parameters
ID –• (000-099) UPS specic information such as serial number, software versions, installation date.
Input –• (100-199) Input measured/calculated data such as input voltage, frequency, current, power,
over-/under- voltage settings.
Output –• (200-299) Output measured/calculated data such as output voltage, frequency, current,
power, over-/under- voltage settings.
Bypass –• (300-399) Bypass data such as conguration, voltage, current, power, OV detection level.
DC Bus –• (400-499) Data such as Total voltage, rated voltage, Positive and Negative bus voltages.
Batt –• (500-599) Battery voltage, charger status, total discharges, shutdown voltage.
Ctrl/Cfg –• (600-699) Control and conguration list system and battery temperatures, system status,
startup delay, auto-transfer window, restart mode.
History –• (700-799) History lists metrics like system operation time, total over loads, hi system temp.
Disp/Reye –• (800-849) Display specic parameters like Disp. Firmware version, sleep timer, buzzer
status, display calibration points, and RemotEye III settings.
(850-859) lists RemotEye III IP address, IP Mask, Status, Baud Rate, datalink status.
On-Line
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
Ctrl/Cfg History
ID Input
Output Bypass
DC Bus Batt
Disp/Reye
Debug
SETTINGS OPENING SCREEN
96% 100%