Toshiba 1600XP Power Supply User Manual


 
55
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
644 Remote SD
Status
Status of Remote Shutdown Contact
- If close, UPS go to shutdown mode if com-
mand id 645 is congured. If open after then it
will go to previous ups mode
Settings C&C Open Nonchangeable
Changeable
User
Administrator
645 Mode of Rmt
SDown
Mode of Remote Shutdown
- Non-volatile conguration. When remote con-
tact is close, it could go to bypass or shutdown.
Settings C&C Shutdown Nonchangeable
Changeable
User
Administrator
646 En DCntct
LANSD
Enable Dry Contact LAN Shutdown
- Non-volatile conguration. Default from fac-
tory is Enable.
Settings C&C Enable Nonchangeable
Changeable
User
Administrator
647 DCntct LANSD
Wndw
Time Window of LAN Shutdown
- Non-volatile conguration. Default from fac-
tory is 600 Seconds
Settings C&C 600 Sec Nonchangeable
Changeable
User
Administrator
648 BK DContact
Delay
Time Delay Remote Contact On Backup
- Non-volatile conguration. Time delay for
Backup dry contact will be on after UPS goes
to Backup Mode. Default from factory is 10 Sec
Settings C&C 10 Sec Nonchangeable
Changeable
User
Administrator
649 LB DContact
Delay
Time Delay Remote Contact On Low Battery
- Non-volatile conguration. Time delay for Low
Battery dry contact will be on after UPS detects
Low Battery warning. Default from factory is 0
Sec
Settings C&C 0 Sec Nonchangeable
Changeable
User
Administrator
652 En Batt Test
Sup*
Enable Battery Test at UPS Startup
- Non-volatile conguration. Default from fac-
tory is Disable
Settings C&C Disable Nonchangeable
Changeable
User
Administrator
653 En Batt Test* Enable or Disable Battery Test
- Non-volatile conguration. Default from fac-
tory is Enable.
Settings C&C Enable Nonchangeable
Changeable
User
Administrator
654 Batt Test Cond Battery Test condition status
- Battery test can be performed if this command
id is enable. It will set by UPS disable accord-
ing to Command Battery test frequency.
Monitor C&C Enable Nonchangeable
Nonchangeable
User
Administrator
655 Batt Test Freq* Max Battery Test Frequency
- Non-volatile conguration. Default from fac-
tory is Monthly.
Settings C&C Monthly Nonchangeable
Changeable
User
Administrator