Toshiba 1600XP Power Supply User Manual


 
50
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
209 Output Load
(%)
Output Load Percentage
- UPS presently calculated output load percent-
age
Monitor OUT 100 % Nonchangeable
Nonchangeable
User
Administrator
215 Rated Vout* Rated Output Voltage
- Must be setup properly at initial startup.
Rated output voltage is used to calculate per-
centages for ID 220, 222
Setting OUT 240 V Nonchangeable
Nonchangeable
User
Administrator
216 Rated Iout Rated Output Current
- UPS calculated rated output current from
typeform command id 002.
Monitor OUT 25.0 A Nonchangeable
Nonchangeable
User
Administrator
217 Rated Fout Rated Output Frequency
-UPS congures output frequency according to
auto or manual mode,
Monitor OUT 60.0 Hz Nonchangeable
Nonchangeable
User
Administrator
218 Rated Pout(W) Rated Output Active Power
- Calculated from typefrom command ID 002.
Monitor OUT 5100 W Nonchangeable
Nonchangeable
User
Administrator
219 Rated Pout(VA) Rated Output Apparent Power
- Calculated from typefrom command ID 002.
Monitor OUT 6000 VA Nonchangeable
Nonchangeable
User
Administrator
220 VOUV De-
Level*
Output Undervoltage Detection Level in Per-
centage
- Of rated output voltage which was congured
with Command ID 215.
Setting OUT 90 % Nonchangeable
Nonchangeable
User
Administrator
222 VOOV De-
Level*
Output Overvoltage Detection Level in percent-
age
- Of rated output voltage which was congured
with Command ID215
Setting OUT 110 % Nonchangeable
Nonchangeable
User
Administrator
224 Fo Syn Win-
dow*
Output Frequency Synchronization Window Setting OUT 1.0 Hz Nonchangeable
Nonchangeable
User
Administrator
226 Vout Adjust Output Voltage Adjustment
- Can adjust up to +/- 5 increment of one in
order to increase or decrease output voltage to
compensate line voltage drop.
Setting OUT 0 Nonchangeable
Changeable
User
Administrator
301 Bypass Cong Bypass Conguration
- Which tell the voltage and frequency 240 V 60
Hz or 208 V 60 Hz
Monitor BYP 240V - 60Hz Nonchangeable
Nonchangeable
User
Administrator
302 No Of Bypass
Line
No of Bypass Lines
- Always 1 input line for 1600XP series
Setting BYP 1 Line Nonchangeable
Nonchangeable
User
Administrator