Toshiba 1600XP Power Supply User Manual


 
53
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
528 Ex Batt C Rate External Battery C rate Settings BATT 0 C Nonchangeable
Nonchangeable
User
Administrator
529 Ex Batt Ins
Date
External Battery Installation Date Settings BATT 01/01/2008 Nonchangeable
Nonchangeable
User
Administrator
545 Low Batt Level* Low Battery Level in Percentage
- Percentage of nominal (# battery in series *
12 Vdc) will issue low battery warning during
Backup
Settings BATT 90 % Nonchangeable
Nonchangeable
User
Administrator
546 VChrgOV De-
Delay
Battery Overvoltage Fault Detection Delay
- Congurable between 0 to 300 Sec
Settings BATT 60 Sec Nonchangeable
Nonchangeable
User
Administrator
547 Cal LB Level Calculated Battery Shutdown Voltage
- Calculated from the discharge rate during
Backup mode
Monitor BATT 194 Vdc Nonchangeable
Nonchangeable
User
Administrator
601 System(CTL)
Temp
Ambient Temperature
- Measured on control PCB
Monitor C&C 26 C Nonchangeable
Nonchangeable
User
Administrator
602 Battery Temp Battery Temperature
- Measured on battery tray
Monitor C&C 25 C Nonchangeable
Nonchangeable
User
Administrator
608 Current State Current UPS State Footer :
Monitor
Right
C&C
On-Line Nonchangeable
Nonchangeable
User
Administrator
609 Requested
State
Requested UPS State Main
Settings
RUN/
STOP
C&C
On-Line Changeable
Changeable
User
Administrator
610 Timed Opera-
tion
Timed Operation Request
- Count down timer to switch UPS operations
Settings C&C On-Line Changeable
Changeable
User
Administrator
611 EPO Status Emergency Power Off Status Monitor C&C Open Nonchangeable
Nonchangeable
User
Administrator
612 Faults UPS Faults
- UPS Faults decoded at footer fault/s eld or
Setting Tab in hex format
Footer:
Setting
Fault/s
Field :
C&C
DVCOH
0X00000008
Nonchangeable
Nonchangeable
User
Administrator
613 Warnings UPS Warnings
- UPS Warnings decoded at footer warning/s
eld or Setting Tab in hex format
Footer:
Setting
Warning/s
Field :
C&C
VIOV
0X00000001
Nonchangeable
Nonchangeable
User
Administrator
615 RunStop SW
Status
Run/Stop Switch Status Monitor C&C Stop Nonchangeable
Nonchangeable
User
Administrator