49
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
136 Input Cur-
rent(%)
Input Current Percentage Monitor IN 100 % Nonchangeable
Nonchangeable
User
Administrator
137 VIUV DeLevel Input Undervoltage Detection
- Calculated according to load and adjusted by
itself.
Monitor IN 190 V Nonchangeable
Nonchangeable
User
Administrator
138 VIUV ReLevel Input Undervoltage Recovery
- Calculated according to load and adjusted by
itself.
Monitor IN 200 V Nonchangeable
Nonchangeable
User
Administrator
139 Rated
InPower(W)
Rated Input Power in Watt
- Calculated from typeform command ID 002.
Monitor IN 6000 W Nonchangeable
Nonchangeable
User
Administrator
141 Freq on FI-
ERR*
Freq setup on input frequency error
- Toshiba UPS try to detect input frequency but
very tiny percentage when UPS can not detect
the input frequency because of uctuation,
1600XP UPS will start by using this setup.
Setting IN 60.0 Hz Nonchangeable
Changeable
User
Administrator
201 Output Cong Output Conguration
- Displays the voltage and frequency
240 V 60 Hz, or 208 V 60 Hz
Monitor OUT 240V - 60Hz Nonchangeable
Nonchangeable
User
Administrator
202 No of Output
Line
No of Output Lines
- Always 1 input line for 1600XP series
Setting OUT 1 Line Nonchangeable
Nonchangeable
User
Administrator
203 Output Voltage Output Voltage
- UPS presently calculated output voltage
Monitor OUT 240 V Nonchangeable
Nonchangeable
User
Administrator
204 Output Current Output Current
- UPS presently calculated output current
Monitor OUT 25.0 A Nonchangeable
Nonchangeable
User
Administrator
205 Output Fre-
quency
Output Frequency
- UPS presently calculated output frequency
Monitor OUT 60.0 Hz Nonchangeable
Nonchangeable
User
Administrator
206 Output
Power(W)
Output Active Power
- UPS presently calculated output active power.
If UPS can not calculate for output active
power, display shows N/A. Especially, bypass
and shutdown
Monitor OUT 5100 W Nonchangeable
Nonchangeable
User
Administrator
207 Output
Power(VA)
Output Apparent Power
- UPS presently calculated output apparent
power.
Monitor OUT 6000 VA Nonchangeable
Nonchangeable
User
Administrator