48
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
101 Input Cong Input Conguration which tell the voltage and
frequency.
Monitor IN 240V - 60Hz Nonchangeable
Nonchangeable
User
Administrator
102 No of Input
Line
No of Input Lines
- Always 1 input line for 1600XP series
Setting IN 1 Line Nonchangeable
Nonchangeable
User
Administrator
103 Input Voltage Input Voltage
- UPS presently calculated input voltage
Monitor IN 240 V Nonchangeable
Nonchangeable
User
Administrator
104 Input Current Input Current
- UPS presently calculated input current
Monitor IN 25.0 A Nonchangeable
Nonchangeable
User
Administrator
105 Input Fre-
quency
Input Frequency
- UPS presently calculated input frequency
Monitor IN 60.0 Hz Nonchangeable
Nonchangeable
User
Administrator
106 Input Power(W) Input Active Power
- UPS presently calculated input active power.
If UPS can not calculate for input apparent
Power, display shows N/A.
Monitor IN 5100 W Nonchangeable
Nonchangeable
User
Administrator
107 Input
Power(VA)
Input Apparent Power
- UPS presently calculated input apparent
power (input voltage * input current)
Monitor IN 6000 VA Nonchangeable
Nonchangeable
User
Administrator
108 Input PFactor Input Power Factor
- If converter is not running, display shows N/A.
Monitor IN 1.0 Nonchangeable
Nonchangeable
User
Administrator
111 Rated Vin* Rated Input Voltage
- Used to calculate percentage and required to
setup properly at very rst time startup.
Setting IN 240 V Nonchangeable
Changeable
User
Administrator
112 Rated Iin Rated Input Current
- Use this setup to calculated percentage.
Monitor IN 25.0 A Nonchangeable
Nonchangeable
User
Administrator
113 Rated Fin Rated Input Frequency
- Detected if auto detection and manual
Monitor IN 60.0 Hz Nonchangeable
Nonchangeable
User
Administrator
119 VIOV DeLevel Input Overvoltage Detection Level
- Of rated input voltage which was congured
with Command ID 111.
Setting IN 274 V Nonchangeable
Nonchangeable
User
Administrator
120 VIOV ReLevel Input Overvoltage Recovery Level - Of rated
input voltage which was congured with Com-
mand ID 111.
Setting IN 264 V Nonchangeable
Nonchangeable
User
Administrator
135 Input Volt-
age(%)
Input Voltage Percentage Monitor IN 100 % Nonchangeable
Nonchangeable
User
Administrator