Toshiba 1600XP Power Supply User Manual


 
54
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
617 SPort Status Service Port Status Monitor C&C Unknown, Idle Nonchangeable
Nonchangeable
User
Administrator
618 Inter Comm
Status
Internal Communication Status
- Veries communication occurring between
display and main controller PCGs
Monitor C&C OK Nonchangeable
Nonchangeable
User
Administrator
619 Security Level Security Level
- Change the password with this command ID
to have different level of security
Settings C&C USER, ADMIN Changeable
Changeable
User
Administrator
620 Manage Admin
PW
Manage Admin Password
- Default is ADMIN
Settings C&C ADMIN Nonchargeable
Changeable
User
Administrator
621 Reset Admin
PW
Reset Admin Password
- Restore administrator’s password to default
ADMIN
Settings C&C Idle Changeable
Changeable
User
Administrator
634 UPS Date UPS Real Time Date (Battery Backup)
- Follow the same format as display shows (
Mon 10/05/2009)
Settings C&C Mon 10/05/2009 Changeable
Changeable
User
Administrator
635 UPS Time UPS Real Time (Battery Backup)
- Use the same format as display shows (12
hour format)
Settings C&C 11:46 AM Changeable
Changeable
User
Administrator
636 Timestamp UPS Real Time Date and Time Stamp
- Used for recording feature
Monitor C&C 0X268AB487 Nonchangeable
Nonchangeable
User
Administrator
637 En REye UPS
Ctl
Enable REye UPS Control
- Enable or disable RemoteEye Network Card
to control UPS modes
Settings C&C Enable Nonchangeable
Changeable
User
Administrator
639 En Startup
Delay*
Enable Startup Time Delay
- Non-volatile conguration. Default from fac-
tory is Disable.
Settings C&C Disable Nonchangeable
Changeable
User
Administrator
640 Startup Mode* Startup UPS Mode
- Non-volatile conguration. Default from fac-
tory is Bypass. It can be changed to On-Line.
Settings C&C Bypass Nonchangeable
Changeable
User
Administrator
641 Startup Delay* Startup Time Delay in Second
- Non-volatile conguration. Default from
factory is zero. You can congure up to 800
Seconds.
Settings C&C 0 Sec Nonchangeable
Changeable
User
Administrator