20
1600XP Series Installation and Operation Manual
STANDARD MODELS: 3.6 – 10 KVA (CONT’D)
Unit (Capacity) 3.6kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
10 kVA (8.5 kW)
1
Environment
Operating Temperature
59 – 77 °F (15 – 25 °C)
Recommended
60 Hz 32 – 104 °F (0 – 40 °C)
50 Hz 32 – 91 °F (0 – 33 °C)
Storage Temperature -4 – 104 °F (-20 – 40 °C)
Installation Area
To be installed in a well ventilated area free of airborne dust,
metal particles or ammable gas, allow at least 4 inches on all sides
Operating Humidity 30 – 90% non-condensing
Altitude < 6600 ft. (2000 m) above sea level
2
Acoustical Noise 50 dB (A) maximum @ 1 meter from front panel
Heat Generation (Typical) 2139 BTU/Hr 3564 BTU/Hr 4095 BTU/Hr 5118 BTU/Hr
Operation Diagnosis
Battery Check Performed on start up, by schedule, on-demand (user congurable)
Input OV Protection Standard
Battery Lifetime
UPS calculates battery replacement time
based upon battery ambient temperature (LCD display, LED and beeps)
Internal Temperature UPS gives indication of internal temperature, alarm when high temp
Event Data Storage 32 – Operation, 32 – Backup, 32 - Warnings, 32 – Faults, 32 - Test, 32 - System
Applications
Switches Generator compatible
Bypass Switch
Bypass Disable Static switch < ¼ cycle (50 Hz – 5 ms/60 Hz – 4.16 ms)
Automatic Retransfer Factory or authorized service center selectable only
Interface/Communications
Real Time Clock Real Time Clock with backup Lithium Ion Battery
Schedule Operation Schedule ON/OFF operation of UPS using optional RemtoEye III communication software
Autostart
Automatic UPS Startup when AC is applied - Option can be enabled or disabled at user’s
discretion
Remote ON/OFF Standard – External terminal
Emergency Power Off Standard – Terminal contacts only
LED Display 3 LED’s indicating On-Line/Fault, Warning, and A/C Input
Operator Interface Interactive Touchscreen
Buzzer Volume Standard (Fixed Volume)
Power Connections Standard – Hard wire, Optional – Receptacle Panel w/ Power Cord
Remote Contacts Standard (INV, BYP, BATT, LB, AC, FLT)
RS232 ASCII Interface Toshiba UPS Communication Protocol 2.0
Input/output gures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid 1.
when the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%2.