Toshiba 1600XP Power Supply User Manual


 
29
1600XP Series Installation and Operation Manual
Operating Modes
On-Line (Run operation)
The following illustration shows circuit power ow when the UPS is operating normally in the On-Line
mode. The UPS rectier, including a boost chopper circuit, converts AC input power to DC power. The
boost chopper circuit maintains a constant voltage, with current limiting, for charging the batteries. It also
supplies a DC voltage of the proper level to the inverter section. The inverter section generates a high
quality sinusoidal output voltage. The unit’s batteries are always maintained in a constantly charged state
when the UPS is in the run operation mode.
Static-Bypass (Stop operation)
If the UPS unit is severely overloaded or develops an internal fault, power ow is automatically switched
from the unit’s main circuit to the bypass circuit. Power ow through the bypass is shown in the following
illustration. This change-over occurs automatically in phase in less than one-quarter cycle of the input
waveform. The switching period is not long enough to cause interruptions to occur in most loads.
If the power ow is transferred to the bypass circuit because of an overload and that overload condition •
ends within a specied period of time then the power ow will be transferred back to the On-Line
mode (run operation) automatically.
If the power ow is transferred to the bypass circuit due to an external • fault the UPS will shut down
power through the bypass to the load and indicate a system fault message.
If the power ow is transferred to the bypass circuit due to an internal fault the UPS will continue to •
supply power to the load through the bypass and indicate a system fault message (see system fault
messages on pages 53–54).
If the power ow is transferred to the bypass circuit due to an overload condition (see system warning •
messages on pages 54–55), then the power ow will automatically transfer from the UPS’s bypass
circuit back to the inverter circuit after removing the overload if set to do so (AutoReXfer parameter
(Cmd ID 662)).
Output
Power
Line Filter Inverter
*Static Switch
Isolation
Transformer
Input
Power
Input
Fuse
Power Flow
Bypass
* Switches are
solid state
devices.
MCCB
Output
Fuse
Surge
Absorber
Batteries
+
Rectier/
Chopper
POWER FLOW IN ON-LINE MODE FOR ALL MODELS
Negative Bus
POWER FLOW IN BYPASS FOR ALL MODELS
Output
Power
Line Filter Inverter
*Static Switch
Isolation
Transformer
Input
Power
Input
Fuse
Power Flow
Bypass
* Switches are
solid state
devices.
MCCB
Output
Fuse
Surge
Absorber
Batteries
+
Rectier/
Chopper
Negative Bus