1600XP Series Installation and Operation Manual
BYPUV Bypass Undervoltage – Bypass
voltage less than UPS specica-
tions.
Depends on UPS mode.
CALL Service Call Required – Inspection
of the unit is advised.
Have inspection/service performed.
CHRGOV Charger Overvoltage – Battery
Charger not within specications.
Contact the nearest Toshiba authorized representa-
tive for service.
CLMT Current Limit – UPS not within
specications.
Contact the nearest Toshiba authorized representa-
tive for service.
DCER Display Cable Error – Display
cable is disconnected.
Connect the display cable.
DDCN Communication Error between
Display and Main Controllers.
Contact the nearest Toshiba authorized representa-
tive for service.
FBYPER Bypass Frequency Error – Input
frequency outside of UPS speci-
cations.
Depends on UPS mode.
FIER Input Frequency Error – Input fre-
quency outside of 45-65 Hz range.
Depends on UPS mode.
LB Low Battery – The battery level
has dropped low (about 90% or
less) during operation. Continued
operation in this mode will deplete
battery and cause output shut
down.
Immediately shut down the load equipment in an
orderly fashion and then press the STOP key.
OL110 Overload – UPS is overloaded
(110% and above) Unit will switch
to bypass operation or shut down
if no action is taken.
Shut down excess equipment to reduce load.
RCER Communication Error between
RemoteEye and UPS.
Ensure RemotEye is connected to UPS. Contact the
nearest Toshiba authorized representative for service.
RSER Communication Error at Service
Port.
Contact the nearest Toshiba authorized representa-
tive for service.
RUER Communication Error at LAN. Contact the nearest Toshiba authorized representa-
tive for service.
VDCUVBT DC Bus Undervoltage During Bat-
tery Test.
Contact the nearest Toshiba authorized representa-
tive for service.
VIOV Input Overvoltage – Input voltage
exceeds UPS specications.
Depends on UPS mode.
VIUV Input Undervoltage – Input voltage
less than UPS specications.
Depends on UPS mode.