56
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
658 En Restart Enable Restart
- Non-volatile conguration. After shutdown by
battery, UPS will restart if input power recover.
Default from factory is Enable.
Settings C&C Enable Nonchangeable
Changeable
User
Administrator
659 Restart Delay Restart Delay Settings C&C 10 Sec Nonchangeable
Changeable
User
Administrator
660 En AutoXfer Enable Auto Transfer
- Non-volatile conguration. Enable auto
transfer when current limit occurs. It will switch
bypass and On-Line mode.
Settings C&C Enable Nonchangeable
Changeable
User
Administrator
662 AutoXfer Win-
dow
Auto Transfer Time Window
- Non-volatile conguration. Default from fac-
tory is 3 Seconds.
Settings C&C 3 Sec Nonchangeable
Changeable
User
Administrator
663 Srv Port Baud* Service Port Baud Rate
- Non-volatile conguration. Default from fac-
tory is 57600.
Settings C&C 57600 Nonchangeable
Changeable
User
Administrator
682 Special
Purpose
(Call Factory for Further Information) Settings C&C Nonchangeable
Nonchangeable
User
Administrator
693 Invert Rmt
SDown
Remoted Shutdown Inverted Logic
- Non-volatile conguration. Default from fac-
tory is Normally Open
Settings C&C Normally Open Nonchangeable
Changeable
User
Administrator
695 Restart Mode* Restart UPS Mode
- Non-volatile conguration. Default from fac-
tory is On-Line
Settings C&C On-Line Nonchangeable
Changeable
User
Administrator
697 Special
Purpose
(Call Factory for Further Information) Settings C&C Nonchangeable
Nonchangeable
User
Administrator
701 System Op
Time
Total System Operation Time
- Non-volatile history record. Default from fac-
tory is zero.
Settings HIST 123 Sec Nonchangeable
Nonchangeable
User
Administrator
702 Inverter Op
Time
Total Inverter Operation Time
- Non-volatile history record. Default from fac-
tory is zero.
Settings HIST 123 Sec Nonchangeable
Nonchangeable
User
Administrator
703 Backup Op
Time
Total Backup Operation Time
- Non-volatile history record. Default from fac-
tory is zero.
Settings HIST 123 Sec Nonchangeable
Nonchangeable
User
Administrator