Electrical Specifications: Charge Mode
445-0089-01-01 A–3
Electrical Specifications: Charge Mode
AC Input
Operating voltage range 90–135Vac
Nominal current 15Aac at 100A charge, 120Vac in
Power factor (100A charge, 120Vac in) ≥0.98 on sine input
Nominal frequency 60Hz
DC Output
Nominal voltage 12.0Vdc
Min battery voltage for charging 0.0Vdc
Max output voltage 17.5Vdc
Nominal output current 100A @ ≤15.0Vdc
Equalize mode max current ≥10A @ ≤17.5Vdc
Charger current derating Automatically reduce charger current as internal
temperature exceeds 80
°C, input Vac
approaches low transfer, and ac input current
approaches 80% of breaker setting.
Efficiency at nominal output ≥84%
Other
Battery type settings Gel, Flooded, AGM, Pb-Ca
Battery size settings 50–2000 Ahr
Charge algorithms Custom 3-stage with factory default set points.
Custom 2-stage as above.
Manually engaged, equalize, with factory
defaults.
CV/CC. User programmable setpoints.
Independent battery banks 1