Xantrex Technology PROsine 2.0 Projector User Manual


 
Introduction
1–10 445-0089-01-01
Adjustable From the Configure Battery Menu
NOTE
Settings below are for Battery Type = Generic Gel.
Battery Size 200Ah **
Default Battery Temperature Warm
Battery Type Generic Gel **
Battery Temp. Coefficient –27mV/°C
Bulk Mode Settings:
Max Voltage
Max Current (%C)
Threshold Voltage
Threshold Timeout
•14.2V
•25%
•13.8V
•3min
Absorption Mode Settings:
Max Voltage
Max Current (%C)
Max Timeout
Threshold Current (%C)
Threshold Timeout
•14.2V
•25%
•8hr
•1%
•3min
Overcharge Mode Settings:
Max Voltage
Max Current (%C)
Max Timeout
•14.2V
•20%
•0
Float Mode Settings:
Max Voltage
Max Current (%C)
Max Timeout
Threshold Voltage
Threshold Timeout
•13.8V
•200%
•21days
•12.5V
15min
Equalize Mode Settings:
Max Voltage
Max Current (%C)
Max Timeout
Threshold Voltage
Threshold Timeout
•13.8V
•200%
•0
•0
•0
Constant Mode Settings:
Voltage Setpoint
Current Setpoint
•13.5V
•100A
Charger Mode Standalone
Charger Type 3-Step
Charger High Battery V
Warning Offset
1.0V
NOTE
The values opposite the gray bar are set when you select a battery type. If you did
not subsequently change these settings, they do not need to be recorded.
Table 1-1
PROsine Default Values
Item Default Value Your Settings