Configuration
4–14 445-0089-01-01
Bulk Charge Mode
Settings
• Max Voltage
This is the maximum available charging voltage for the Bulk charging stage.
• Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Bulk charging stage.
• Threshold Voltage and Timeout
When the battery voltage goes above this value for the Threshold Timeout
specified, the unit goes into Absorption charging stage.
Absorption Mode
Settings
• Max Voltage
This is the maximum charging voltage for the Absorption charging stage.
Typically, the battery will be at this voltage for the duration of this stage.
• Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Absorption charging stage.
• Max Timeout
This is the maximum amount of time that the unit will stay in the Absorption
stage.
• Threshold Current (%C) and Timeout
When battery current goes below this value (A as % of battery capacity in Ah)
for the Threshold Timeout, the unit goes into the next charging stage.
Overcharge Mode
Settings
• Max Voltage
This is the maximum charging voltage for the Overcharge charging stage.
Typically the battery will be at this voltage for the duration of this stage.
• Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Overcharge charging stage.
• Max Timeout
The amount of time that the Overcharge stage will run.
Float Mode Settings • Max Voltage
This is the maximum available charging voltage for the Float charging stage.
Typically the battery will be at this voltage for the duration of this stage.
• Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Float charging stage.
• Max Timeout
This is the maximum amount of time that the charger will be in Float stage.
• Threshold Voltage and Timeout
When the battery voltage goes below this value for the Threshold Timeout
specified, the unit goes into Bulk charging mode.