Xantrex Technology PROsine 2.0 Projector User Manual


 
Part 3: Configuration Options
445-0089-01-01 4–7
Configure PROsine—Basic Menu
Menu Choices or Information Displayed
AC Breaker Size Set the AC breaker size to match the shorepower circuit breaker size to reduce
circuit breaker “nuisance” tripping. Values range from 0–30 amps.
Load Sensing Select Enabled if you want the unit to only turn on when a load is present. In
Load Sense mode, the unit will periodically search for the presence of an AC load
while it is inverting. The unit will “sleep” if the load it detects is less than the
Load Sensing setting or if there is no load.
Select Disabled if you want the inverter on full-time rather than only when a load
is present.
For further information about load sensing, see “Load Sensing Mode” on page 5–
5.
Equalize Select Enabled or Disabled. You can only select Enabled when the unit is
charging and battery type is set to Flooded.
An equalization charge must only be performed on flooded (non-sealed or “wet”)
batteries and only as often as recommended by the battery manufacturer.
Menu Items Access
AC Breaker Size User
Load Sensing User
Equalize User
WARNING: Fire hazard
If you select Enabled, you must monitor the electrolyte specific gravity and level during
the equalization phase to prevent over-heating and battery damage.
CAUTION
During the equalization phase, the DC system voltage may exceed 17VDC, and therefore
you should disconnect any sensitive DC loads.