6-18 ADAM-5000
Command Set
Error Code Error Message
00h No errors
01h Span calibration error of Analog Input Module
02h Self-calibration error of Analog Input Module
04h Zero calibration error of Analog Input Module
08h Data Reading error of Analog Input Module
10h CJC Reading error
20h EEPROM read/write error in AI/AO module
Figure 6-2 Analog module error codes
Example: command: $01E(cr)
response: !0100000001
The command diagnoses the system at address 01h and
responds with its error status code.
The system responds that the module in slot 3 has a