Command Set
#aaSi #aaSi
Name All Analog Data In
Description Returns the input value of all channels for a specified
analog input module of a specified system in engineer-
ing unit only.
Syntax #aaSi(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
Si is the I/O slot of ADAM-5000 system you want to
read.
(cr) is the terminating character, carriage return (0Dh)
Response >(data) (data) (data) (data) (data) (data) (data) (data) (cr) if
the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
> is a delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
(data) is the input value in engineering units of a channel
in the interrogated module of the specified system. The
(data) from all channels is shown in sequence from 7 to
0. If (data) = “ ”, it means the channel is invalid.
(cr) is the terminating character, carriage return (0Dh)