Advantech RS-485 Barcode Reader User Manual


 
6-92 ADAM-5000
Command Set
$aaSiCjArrff $aaSiCjArrff
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh)
Example command: $35S3C0A3110(cr)
response: !35(cr)
The analog output channel 0 in slot 3 of the ADAM-
5000 system at address 35h is configured to an output
range 4 to 20mA, engineering units data format, and a
slew rate of 1.0mA/sec.
The response indicates that the command has been
received.
Note: An analog output module requires a maximum of 20
milliseconds to perform auto calibration and ranging
after it is reconfigured. During this time span, the
module cannot be address to perform any other
actions.
Figure 6-4 Data format of 8-bit parameters
5024 Analog Output