Advantech RS-485 Barcode Reader User Manual


 
ADAM-5000 B-5
Appendix B
Module Range
Code
Input Range
Description
Data Formats +F.S. Zero -F.S. Displayed
Resolution
Engineering
Units
+15.000 ±00.000 -15.000 1 µV
00h ±15 mV % of FSR +100.00 ±000.00 -100.00 0.01%
Two 's
Complement
7FFF 0000 8000 1 LSB
Engineering
Units
+50.000 ±00.000 -50.000 1 µV
01h ±50 mV % of FSR +100.00 ±000.00 -100.00 0.01%
Two 's
Complement
7FFF 0000 8000 1 LSB
Engineering
Units
+100.00 ±000.00 -100.00 10 µV
ADAM-
5018
02h ±100 mV % of FSR +100.00 ±000.00 -100.00 0.01%
Two 's
Complement
7FFF 0000 8000 1 LSB
Engineering
Units
+500.00 ±000.00 -500.00 10 µV
03h ±500 mV % of FSR +100.00 ±000.00 -100.00 0.01%
Two 's
Complement
7FFF 0000 8000 1 LSB
Engineering
Units
+1.0000 ±0.0000 -1.0000 100 µV
04h ±1 V % of FSR +100.00 ±000.00 -100.00 0.01%
Two 's
Complement
7FFF 0000 8000 1 LSB
Engineering
Units
+2.5000 ±0.0000 -2.5000 100 µV
05h ±2.5 V % of FSR +100.00 ±000.00 -100.00 0.01%
Two 's
Complement
7FFF 0000 8000 1 LSB
Engineering
Units
+20.000 ±00.000 -20.000 1 µA
06h ±20 mA % of FSR +100.00 ±000.00 -100.00 0.01%
Two 's
Complement
7FFF 0000 8000 1 LSB
07h Not Used