ADAM-5000 6-97
Chapter 6
$aaSiCj4 $aaSiCj4
Name Start-Up Output Current/Voltage Configuration
Description Stores a default output value in a specified channel. The
output value will take effect upon startup or reset.
Syntax $aaSiCj4(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system.
SiCj identifies the I/O slot i (i : 0 to 3) and the channel j (j
: 0 to 3) of the module you want to set.
4 is the Start-Up Output Current/Voltage Configuration
command.
(cr) is the terminating character, carriage return (0Dh)
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh)