Connections to Inter-bay Busbars (P/O List 2)
Note: Battery busbars within distribution cabinets are rated for 2000A max.
For 2000A-4000A in List 2, make battery connections to inter-bay busbars, shown here.
DETAIL A
1"
2-3/8"
2-3/8" 2-3/8"
5/8"
3/4"3/4"3/4"
1-5/8" 1-5/8"
3/8-16 CAPTIVE NUT, 8 PLACES PER BUS
(CUSTOMER MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")
1/4-20 CAPTIVE NUT, 12 PLACES PER BUS
(CUSTOMER MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")
13/16"
13/16"
13/16"
13/16"
GND RETURN
Interbay Busbar Assembly
+24V SUPPLY
Interbay Busbar Assembly
Battery Lug
Landing Points
See Detail A
Rear View