Emerson SAG581126000 Power Supply User Manual


 
System Application Guide SAG581126000
Spec. No. 581126000 (Model 700
NVBA) Issue AD, November 23, 2009
Page 73 of 123
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
GMT-Type Load Distribution Fuses
Features
An optional “
GMT Load Distribution Fuse Block Assembly Kit” (see previous section) is available for
additional load distribution.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 amp fuses,
for which load should not exceed 70% of device rating.
Ordering Notes
1) Order fuses as required per
Table 2 (GMT Fuses).
Ampere Rating Part Number Fuse Color
18/100 (GMT-A) 248610301 ---
1/4 248610200 VIOLET
1/2 248610300 RED
3/4 248610500 BROWN
1-1/3 248610700 WHITE
2 248610800 ORANGE
3 248610900 BLUE
5 248611000 GREEN
7-1/2 248611300 BLACK-WHITE
10 248611200 RED-WHITE
15 248611500 RED-BLUE
Replacement
Safety Fuse
Cover (GMT-Y)
102774 ---
Replacement
Dummy Fuse
248872600 ---
Table 2
GMT Fuses