SAG581126000 System Application Guide
Issue AD, November 23, 2009 Spec. No. 581126000 (Model 700
NVBA)
Page 64 of 123
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List ND: Distribution Bus Module (P/N 514030)
(2) TPH Fuse Battery Disconnect Positions
Features
♦ Single Voltage Distribution (+24V)
♦ 960A Maximum Capacity
♦ (2) Battery Disconnect Fuse Mounting Positions
(70 to 600A TPH-Type)
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.
Ordering Notes
1) Order fuses as required per
Table 4. Order replacement alarm fuses (1/4A) per Table 3.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position
per Table
10.
1"
BATTERY DISCONNECTS
BATTERY
(LOAD SIDE)
CONNECTIONS
BATTERY
(LOAD SIDE)
CONNECTIONS
2-1/8"
2-1/8" 2-1/8" 2-1/8"
3/8-16 CAPTIVE NUT, 12 PLACES (CUSTOMER MUST
SUPPLY LUG BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")
Home