Emerson SAG581126000 Power Supply User Manual


 
System Application Guide SAG581126000
Spec. No. 581126000 (Model 700
NVBA) Issue AD, November 23, 2009
Page 35 of 123
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List AC: Distribution Bus Module (P/N 507198)
(3) GJ/218 Circuit Breaker System Positions
Features
Single Voltage Distribution (+24V)
500A Maximum Capacity
(3) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type) NOTE RESTRICTIONS
Restrictions
For use in a 4-bus row cabinet only. Must be installed in bus position D (row 4). See also
List AB for similar
application in bus positions A-C (rows 1-3).
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables
5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position
per Table
10.
1"
1.5"
1"
1"
LOADS
1"
LOAD
CONNECTIONS
GROUND
BUSBAR
LOAD RETURN
CONNECTIONS
3/8-16 CAPTIVE NUT, 12 PLACES
(CUSTOMER MUST SUPPLY LUG
BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")