List NB: Distribution Bus Module (P/N 513809)
(3) GJ/218 Circuit Breaker Battery Disconnect Positions
Features
Single Voltage Distribution (+24V)
500A Maximum Capacity
(3) Battery Disconnect Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type) NOTE RESTRICTIONS
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A or B (row 1 or 2) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in second row of a 3-bus row cabinet in List 1 if used with List 2.
Cannot be used in second row of a 3-bus row cabinet in List 2.
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables
5 and 6.
2) Order battery lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position
per Table
10.
1"
1"
1"
BATTERY DISCONNECT
BATTERY (LOAD SIDE)
CONNECTIONS
3/8-16 CAPTIVE NUT, 6 PLACES
(CUSTOMER MUST SUPPLY LUG
BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")