Recm 90°C Wire Size
(1)
4 AWG 2 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG
250
kcmil
350
kcmil
Fuse/
Circuit
Breaker
Amperage
Loop Length (feet)
(2)
90A
41
(3)
66
(3, 4)
105
(3, 4)
133
(4)
-- -- -- --
100A
-- 59
(3, 4)
95
(3, 4)
119
(3, 4)
-- -- -- --
125A
-- 47
(3)
76
(3, 4)
95
(3, 4)
120
(4)
-- -- --
150A
-- -- 63
(3, 4)
79
(3, 4)
100
(3, 4)
-- -- --
200A
-- -- -- -- 75
(3, 4)
95
(3, 4)
112
(3, 4)
--
250A
-- -- -- -- -- 76
(3, 4,
7)
90
(3, 4,
7)
126
(3, 4,
7)
Recommended Crimp Lug
Lug
(5)
245346800 245346900
245393500
(6)
245393600
(6)
245393700
(6)
245393800
(6)
514872
(6)
514873
(6)
Lug
(8, 9)
-- 245348200 245347100 245347200 245347300 245347400 245347500 245347700
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30°C and 40°C was used. For other operating
ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized,
follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping
information.
6
Special application crimp lug / strap combination.
7
MUST USE P/N 514717 Lug Adapter Busbar for lugs having 1/4" bolt clearance hole, 5/8" centers.
8
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
9
MUST USE P/N 534449 Lug Adapter Busbar Kit for 125-200A circuit breakers or P/N 514714 Lug
Adapter Busbar Kit for 250A circuit breakers.
Table 12 (cont'd from previous page)
Recommended Wire Sizes and Lugs for Load and Battery Connections
to Various TPS/TLS Fuses and Bullet Nose-Type Circuit Breakers
or Battery Branch Circuits
Home