Recm 90°C Wire Size
(1)
2/0 AWG 3/0 AWG 4/0 AWG
250
kcmil
300
kcmil
350
kcmil
400
kcmil
500
kcmil
Fuse/
Circuit
Breaker
Amperage
Loop Length (feet)
(2)
225A
-- 67
(3)
84
(3, 4)
100
(3, 4)
120
(4)
-- -- --
250A
-- -- 76
(3)
90
(3, 4)
108
(3, 4)
126
(4)
-- --
300A
159
(4)
(2) Wires
-- -- -- 90
(3)
105
(3, 4)
120
(3, 4)
--
400A
--
75
(3, 4)
(2) Wires
95
(3, 4)
(2) Wires
112
(3, 4)
(2) Wires
-- -- -- --
500A
-- --
76
(3)
(2) Wires
90
(3, 4)
(2) Wires
108
(3, 4)
(2) Wires
126
(4)
(2) Wires
-- --
600A
-- -- -- --
90
(3)
(2) Wires
105
(3, 4)
(2) Wires
157
(4)
(3) Wires
120
(3, 4)
(2) Wires
--
Recommended Crimp Lug
(5)
Lug
245347200
(per cable)
245347300
(per cable)
245347400
(per cable)
245347500
(per cable)
245347600
(per cable)
245347700
(per cable)
245347800
(per cable)
245347900
(per cable)
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30°C and 40°C was used. For other operating
ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized,
follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
Table 13 (cont'd from previous page)
Recommended Wire Sizes and Lugs for Load and Battery Connections
to Various TPH Fuses and GJ/218-Circuit Breakers