List NC: Distribution Bus Module (P/N 514025)
(1) TPH Fuse Battery Disconnect Position
Features
Single Voltage Distribution (+24V)
500A Maximum Capacity
(1) Battery Disconnect Fuse Mounting Position
(70 to 600A TPH-Type)
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Ordering Notes
1) Order fuses as required per
Table 4. Order replacement alarm fuses (1/4A) per Table 3.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position
per Table
10.
1"
1"
BATTERY
DISCONNECT
GROUND
BUSBAR
BATTERY
(RETURN SIDE)
CONNECTIONS
BATTERY (LOAD SIDE)
CONNECTIONS
2-1/8"
2-1/8"
2-1/8"
2-1/8"
3/8-16 CAPTIVE NUT, 12 PLACES (CUSTOMER MUST
SUPPLY LUG BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")