Emerson SAG581126000 Power Supply User Manual


 
System Application Guide SAG581126000
Spec. No. 581126000 (Model 700
NVBA) Issue AD, November 23, 2009
Page 65 of 123
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List RA: 1200A Low Voltage Battery Disconnect (LVBD)
Contactor and Control Circuit (P/N 540808)
Features
Provides a battery disconnect contactor, which is mounted in bus position A (row 1) of the Distribution
Cabinet.
Restrictions
Limit one bus arrangement of this type per System.
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used with List 92, 93, RB, RC, RD, or RE.
Ordering Notes
1) Order as required.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Table
10.
1"
1-1/4"
1-1/4"
BATTERY
(LOAD SIDE)
CONNECTIONS
CLEARANCE HOLES FOR 3/8 BOLT, 2 PLACES
FOR MOUNTING LUG ON BACK SIDE OF BUSBAR
(CUSTOMER MUST PROVIDE LUG BOLTS, NUTS AND
ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")
3/8-16 CAPTIVE NUT, 4 PLACES
(CUSTOMER MUST PROVIDE LUG
BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")
Home