Emerson SAG581126000 Power Supply User Manual


 
SAG581126000 System Application Guide
Issue AD, November 23, 2009 Spec. No. 581126000 (Model 700
NVBA)
Page 40 of 123
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List AJ: Distribution Bus Module (P/N 520819)
(2) TPH Fuse System Positions with Load Metering Shunts
Features
Single Voltage Distribution (+24V)
500A Maximum Capacity
(2) Distribution Fuse Mounting Positions
(70 to 600A TPH-Type)
(1) Load Shunt (800A, 50mV) per load fuse is provided. Extended shunt leads are 22 AWG stranded
wire, approximately 7-10 ft. long from exit point at bottom of Distribution Cabinet. Each shunt lead is
equipped with a 49.9 ohm current limiting resistor.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Does not provide connection for load returns (see Ordering Notes).
Ordering Notes
1) To terminate load returns within the distribution cabinet, order one (1)
List AH for up to two (2) List AJ.
2) Order fuses as required per
Table 4. Order replacement alarm fuses (1/4A) per Table 3.
3) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position
per Table
10.
1"
2-1/8"
LOAD
CONNECTIONS
LOAD
CONNECTIONS
LOAD
2-1/8" 2-1/8" 2-1/8"
3/8-16 CAPTIVE NUT,
6 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")
3/8-16 CAPTIVE NUT,
6 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")
LOAD
Home