Multi-Tech Systems 7600 Network Card User Manual


 
ION 7500 / ION 7600 User’s Guide Alerting via an Alphanumeric Pager
Chapter 5 - Features and Applications Page 155
Alerting via an Alphanumeric Pager
NOTE
For detailed information about building a framework for alerting via an alphanumeric pager, refer to the
Alert module description in the online
ION Programmer’s Reference.
If an alphanumeric pager is specified as the destination address in the Alert
module, then an alphanumeric paging service receives a message from the ION
meter.
Once the modem at the paging service is contacted, the ION meter transmits the
following information:
Pager identification number
Local time (year, month, date, hours, minutes, seconds)
Remote site identification
Priority of the alarm
Alert message, with text strings and realtime measured values
To include a module’s Source input in the message, reference the message string by
using the form %Vn, where n is the Source input number. In the following Message
register setting, the kWtot value is %V1. The string includes Source input 1 which
would be the kWtot register from the Power Meter module.
The destination register contains your modem access number for the paging
service provider and is what is dialed out first. The Pager Num register is the pager
access number that is provided by your paging company.