Using the Modbus RTU Protocol ION 7500 / ION 7600 User’s Guide
Page 72 Chapter 3 - Default Meter Functionality
Phase V kVA kVA c Power Meter Modbus Slave #2 – Source Input #11 40047-40048
Total kVA kVA tot Power Meter Modbus Slave #2 – Source Input #12 40049-40050
Phase A signed PF PF sign a Power Meter Modbus Slave #2 – Source Input #13 40051-40052
Phase B signed PF PF sign b Power Meter Modbus Slave #2 – Source Input #14 40053-40054
Phase C signed PF PF sign c Power Meter Modbus Slave #2 – Source Input #15 40055-40056
Average signed PF PF signed tot Power Meter Modbus Slave #2 – Source Input #16 40057-40058
Measurement Label Source ION Module Modbus Module and Input Number Modbus Register
Maximum Avg L-L Voltage Vll avg mx Maximum Modbus Slave #3 – Source Input #1 40059 to 40060
Maximum Average Current I avg mx Maximum Modbus Slave #3 – Source Input #2 40061 to 40062
Maximum Total kW kW tot mx Maximum Modbus Slave #3 – Source Input #3 40063 to 40064
Maximum Total kVAR kVAR tot mx Maximum Modbus Slave #3 – Source Input #4 40065 to 40066
Maximum Total kVA kVA tot mx Maximum Modbus Slave #3 – Source Input #5 40067 to 40068
Maximum Line Frequency Freq mx Maximum Modbus Slave #3 – Source Input #6 40069 to 40070
Minimum Avg L-L Voltage Vll avg mn Minimum Modbus Slave #3 – Source Input #7 40071 to 40072
Minimum Average Current I avg mn Minimum Modbus Slave #3 – Source Input #8 40073 to 40074
Minimum Line Frequency Freq mn Minimum Modbus Slave #3 – Source Input #9 40075 to 40076
kW Sliding Window Demand kW sd del-rec Sliding Win Demand Modbus Slave #3 – Source Input #10 40077 to 40078
kVA Sliding Window Demand
KVA sd
del+rec
Sliding Win Demand Modbus Slave #3 – Source Input #11 40079 to 40080
kVAR Sliding Window
Demand
kVAR sd del-
rec
Sliding Win Demand Modbus Slave #3 – Source Input #12 40081 to 40082
Maximum kW SW Demand
kW sd mx
del-rec
Maximum Modbus Slave #3 – Source Input #13 40083 to 40084
Maximum kVA SW Demand
kVA sd mx
del+rec
Maximum Modbus Slave #3 – Source Input #14 40085 to 40086
Maximum kVAR SW Demand
kVAR sd mx
del-rec
Maximum Modbus Slave #3 – Source Input #15 40087 to 40088
Phase reversal indicator
(0=no reversal; 1=reversal)
Phase Rev Power Meter Modbus Slave #3 – Source Input #16 40089 to 40090
Measurement Label Source ION Module Modbus Module and Input Number Modbus Register
Imported kWh kWh del Integrator Modbus Slave #4 – Source Input #1 40091 to 40092
Exported kWh kWh rec Integrator Modbus Slave #4 – Source Input #2 40093 to 40094
Total kWh kWh del+rec Integrator Modbus Slave #4 – Source Input #3 40095 to 40096
Net kWh kWh del-rec Integrator Modbus Slave #4 – Source Input #4 40097 to 40098
Imported kVARh kVARh del Integrator Modbus Slave #4 – Source Input #5 40099 to 40100
Measurement Label Source ION Module Modbus Module and Input Number Modbus Register