Multi-Tech Systems 7600 Network Card User Manual


 
ION 7500 / ION 7600 User’s Guide Display Setup
Chapter 3 - Default Meter Functionality Page 63
Display Setup
The meter’s front panel display is controlled by three types of ION modules: the
Display Options module, the Scroll module, and Display modules.
Display Options Module Settings
The Display Options module contains setup registers that hold data display
settings such as contrast level, backlight timeout, daylight savings time, and
update time. Settings in the Display Options modules are global, and affect the
entire set of front panel display screens.
Scroll Module Settings
The Scroll module determines the sequence and rate of scrolling for multiple front
panel display screens.
The Trigger outputs of Scroll module are linked to the inputs of Display modules.
When a pulse is sent from the Trigger output of a Scroll module to a linked Display
module, the Display module shows its information on the front panel.
Display Module Settings
Display modules determine the form and content of each display screen
.
Setup Register Function Default
Contrast Sets the global contrast setting for the meter display. 7
Backlight Timeout
Sets the time that the front panel’s backlight stays on after the last press of a front
panel button (in seconds).
300
Display Update Time Sets the period between data display refreshes (in seconds). 1
Digital Grouping
Sets the numbering format by determining how groups of three digits are
separated.
1,000
Demand Lockout Timeout Sets the minimum time allowed between consecutive demand resets. 2,160,000
Setup Register Function Default
Scroll Delay
Sets the time that will elapse between successive pulses on the
Trigger
outputs when the
scroll module is enabled.
6
Wraparound
Designates the last
Trigger
output (
Trigger
n) before returning to the first
Trigger
in
he order.
10
Freeze Time
Sets the time (in seconds) that the Scroll module remains "frozen" when pulsed from the
Freeze
,
Up
, or
Down
inputs.
120
Setup Register Function Default
Screen Type
This specifies the way the linked parameters are displayed on the front panel
screen.
Defaults vary among display
screens. Refer to the
ION
Device Templates
at
www.pwrm.com.
Softkey Number This assigns a softkey number to the display screen.
Softkey Name This assigns a softkey name to the display screen.
Screen Title This assigns a title to the display screen.