7. Pk Dmd1 (Peak Demand Del)
This is a numeric display screen with timestamps that contains maximum
delivered demand values for kW, kVAR, and kVA. The timestamps show the
date and time at which the values were last updated. By default, these values
come from a sliding window demand calculation.
8, 9, 10. V Bar, I Bar, P Bar (Voltage, Current, and Power Bar Graphs)
These three screens are trend bar graph displays. They show real time values for
voltage (Vll ab, Vll bc, Vll ca, Vll avg), current (I a, I b, I c, I avg) and
power (kW tot, kVAR tot, kVA tot, PF lag tot). The bar graphs also indicate the
maximums and minimums recorded for these values.
Additional Data Display Screens
Most of the default data screens are not included in the default scrolling cycle. To
view the other display screens, you must find the group of five Softkey titles that
contains the data screen you want, and then press the corresponding Softkey.
NOTE
The numbers on the left correspond to the Display module’s Softkey number in the ION 7600 meter’s
display framework. The Softkey numbering for an ION 7500 differs slightly due to V trend, I trend, and
P trend taking the place of Softkeys 13, 14, and 15 respectively. The ION 7500 does not support display
screens for EN50160 data and statistics.
11. Summary1 (Volts/Amps Summary)
This numeric display provides many important voltage, current, phase, and
frequency measurements on a single screen.
12. Summary2 (Power Summary)
This numeric display provides real, reactive, and apparent power
measurements for phase a, b and c (as well as their total). Signed Power Factor
measurements are also provided on this screen.
13. D Inputs (Digital Inputs)
This numeric display screen shows the status of the eight on-board digital
inputs. The present state of all inputs is shown (as Off or On) and the number
(Cnt) of state changes since the last reset is recorded.
14. DI - I/O (DI on I/O Card)
This numeric display screen contains the status and counters for the digital
inputs on the I/O card.
15. D Outputs (Digital Outputs)
This numeric display screen contains the mode and status for the relay and solid
state outputs.
16. Anlg - I/O (Analog In and Out)
This numeric display screen contains scaled analog inputs (AIn scaled) and
normalized analog outputs (AOn normalized), where n ranges from 1 to 4 for