Multi-Tech Systems 7600 Network Card User Manual


 
ION 7500 / ION 7600 User’s Guide Harmonic Voltage
Power Quality: ION Meters and EN50160 Technical Note Page 317
Harmonics Default Measurements
Register Label Source Module Description
V1-Hrm N*
Harmonics
Evaluation
number of valid intervals (voltage on phase 1 within +/- 15% of nominal)
V1-Hrm N invld* number of invalid intervals
V1-Hrm N1* number of intervals in which one or more individual harmonics on phase 1 exceed their limits
V1-Hrm N2* number of intervals in which the THD value on phase 1 exceeds the limit
V2-Hrm N* number of valid intervals (voltage on phase 2 within +/- 15% of nominal)
V2-Hrm N invld* number of invalid intervals
V2-Hrm N1* number of intervals in which one or more individual harmonics on phase 2 exceed their limits
V2-Hrm N2* number of intervals in which the THD value on phase 2 exceeds the limit
V3-Hrm N* number of valid intervals (voltage on phase 3 within +/- 15% of nominal)
V3-Hrm N invld* number of invalid intervals
V3-Hrm N1* number of intervals in which one or more individual harmonics on phase 3 exceed their limits
V3-Hrm N2* number of intervals in which the THD value on phase 3 exceeds the limit
PO V1-Hrm N
Store
V1-Hrm N of the previous Observation Period
PO V1-Hrm N1 V1-Hrm N1 of the previous Observation Period
PO V1-Hrm N2 V1-Hrm N2 of the previous Observation Period
PO V2-Hrm N V2-Hrm N of the previous Observation Period
PO V2-Hrm N1 V2-Hrm N1 of the previous Observation Period
PO V2-Hrm N2 V2-Hrm N2 of the previous Observation Period
PO V3-Hrm N V3-Hrm N of the previous Observation Period
PO V3-Hrm N1 V3-Hrm N1 of the previous Observation Period
PO V3-Hrm N2 V3-Hrm N2 of the previous Observation Period
V1 THD mean
Sliding Window
Demand
average THD on phase 1 over 10 minutes (used for display purposes)
V2 THD mean average THD on phase 2 over 10 minutes (used for display purposes)
V3 THD mean average THD on phase 3 over 10 minutes (used for display purposes)
V1 THD mean mn
Minimum
minimum average THD on phase 1 over 1 week (used for display purposes)
V2 THD mean mn minimum average THD on phase 2 over 1 week (used for display purposes)
V3 THD mean mn minimum average THD on phase 3 over 1 week (used for display purposes)
V1 THD mean mx
Maximum
maximum average THD on phase 1 over 10 minutes (used for display purposes)
V2 THD mean mx maximum average THD on phase 2 over 1 week (used for display purposes)
V3 THD mean mx maximum average THD on phase 3 over 1 week (used for display purposes)