122188-10 A0 Telect, Inc. 3-1
3 User Functions
THE ALARM CUTOFF/LAMP BUTTON
Each system has an Alarm Cutoff (ACO)/Lamp Button located on the LED
panel that disables the external alarm contacts and tests the LEDs.
Disabling Alarms
To disable the external alarm contacts, press and release the button marked
ACO/LMP.
The ACO LED lights and the alarms are disabled for the length of time
specified in the System Settings screen of the craft interface
1
or through
SNMP.
Testing LEDs and Resetting the ACO
As part of the LED test, the ACO is reset (the alarms are enabled). If the
alarms are disabled when you test the LEDs, you must disable them again
(see above) when the test is complete to return them to their previous state.
1. See “Specifying System Settings & M13 Card Functions” on page 4-14.
Alarm Cutoff/
Lamp Button
Alarm Cutoff
(
ACO
)
CRAFT
HS
CRT MJR
MNR MAINT
LS
ACO
ACO/LAMP