Agilent Technologies 85330A Network Card User Manual


 
4-10 85330A Multiple Channel Controller
General Information
85330A Multiple Channel Controller Characteristics
Ventilation
Requirements
CAUTION When installing the product in a cabinet, the convection into and out of the
product must not be restricted. The ambient temperature (outside the
cabinet) must be less than the maximum operating temperature of the
product by 4
°C for every 100 watts dissipated in the cabinet. If the total
power dissipated in the cabinet is greater than 800 watts, then forced
convection must be used.
Dimensions
Table 4-4 Size and Dimensions
Height without feet 177 mm 6.97 in
Height with feet 189 mm 7.44 in
Width 426 mm 16.75 in
Depth 510 mm 20.1 in
Depth with terminal blocks 569 mm 22.38 in
Net weight
11.8 kg 26 lbs