Dell Command Line Interface Network Card User Manual


 
Using the Storage Management Service 183
Example for SCSI, SATA, and ATA Controllers:
In this example, temperature probe 3 resides in the enclosure attached to connector 2 on controller 1.
To set the temperature probe thresholds to 10 and 40
° Celsius, enter:
omconfig storage enclosure action=settempprobes controller=1
enclosure=2 index=3 minwarn=10 maxwarn=40
omconfig Reset Temperature Probe Thresholds
Use the following omconfig command syntax to reset the minimum and maximum warning temperature
thresholds back to their default values.
NOTE: This command is not supported on SAS controllers.
Complete Syntax
omconfig storage enclosure action=resettempprobes controller=id
enclosure=<ENCLOSUREID> index=id
where id is the controller ID and the temperature probe ID. The <ENCLOSUREID> variable specifies
the enclosure.
Example Syntax
For example, you may want to reset the thresholds for temperature probe 3 to the default values.
Example for SCSI, SATA, and ATA Controllers:
In this example, temperature probe 3 resides in the enclosure attached to connector 2 on controller 1.
To reset the thresholds for temperature probe 3 to the default values, enter:
omconfig storage enclosure action=resettempprobes controller=1
enclosure=2 index=3
omconfig Set All Temperature Probe Thresholds
Use the following omconfig command syntax to set the minimum and maximum warning temperature
thresholds for all temperature probes in the enclosure.
NOTE: This command is not supported on SCSI RAID controllers.
Complete Syntax
omconfig storage enclosure action=setalltempprobes controller=id
enclosure=<ENCLOSUREID> minwarn=n maxwarn=n
where id is the controller ID. The <ENCLOSUREID> variable specifies the enclosure.