Chapter 7 Servo Parameters|ASDA-B Series
Revision January, 2009 7-65
NOTE
1) When P2-08 is set to 10, users cannot reset this parameter.
P4 - 17 COF3 Current Detector Drift Adjustment (W1 phase) Communication Addr.: 0411H
Default: Factory setting Related Section:
Applicable Control Mode: P/S/T P4-10
Unit: N/A
Range: 0 ~ 32767
Settings:
Manual Adjustment Operation:
Set parameter P2-08 to 22 and then change this parameter. This is an auxiliary adjusting
function, although this parameter allows the users can execute manual adjustment, we still do
not recommend users to change the default setting manually.
Auto Adjustment Operation:
Set parameter P2-08 to 20 first and then set parameter P4-10 to 4.
When executing this auto adjustment, ensure that the servo system should be off (Servo off) and
the servo motor has stopped.
NOTE
1) When P2-08 is set to 10, users cannot reset this parameter.
P4 - 18 COF4 Current Detector Drift Adjustment (W2 phase) Communication Addr.: 0412H
Default: Factory setting Related Section:
Applicable Control Mode: P/S/T P4-10
Unit: N/A
Range: 0 ~ 32767
Settings:
Please see P4-17 for explanation.
NOTE
1) When P2-08 is set to 10, users cannot reset this parameter.
P4 - 19
TIGB IGBT NTC Calibration Communication Addr.: 0413H
Default: Factory setting Related Section:
Applicable Control Mode: P/S/T Parameter P4-10
Unit: N/A
Range: 1 ~ 3