Delta Electronics ASDA-B Series Network Card User Manual


 
Chapter 7 Servo Parameters|ASDA-B Series
Revision January, 2009 7-69
1: If 1 is set, it indicates the keypad is the master side during communication. 1 must be set
when communicating with servo drive, or there will be a communication fault.
Keypad Parameter Reset Function Settings:
0: Disable keypad parameter reset function.
1: Enable keypad parameter reset function. All keypad parameter settings will be reset to
default setting if this function is selected. (All keypad parameter settings will be cleared after
this function is executing.)
After parameter P8-01 is set, users must restart the servo drive (switching power off and on).
P8 - 02 Reserved Communication Addr.: 0802H
P8 - 03 Reserved Communication Addr.: 0803H
P8 - 04 Reserved Communication Addr.: 0804H
P8 - 05 KADR Communication Address Setting (Drive) Communication Addr.: 0805H
Default: 255 Related Section: N/A
Applicable Control Mode: P/S/T
Unit: N/A
Range: 1 ~ 255
Settings:
If the AC servo drive is controlled by RS-232/485 communication, each drive (or device) must be
uniquely identified and addressed between 1 and 255.
One servo drive only can set one communication address.
If the address is duplicated, there will be a communication fault.
When the address is set to 255, it is with auto communication function.
P8 - 06 KBRT Transmission Speed (Keypad) Communication Addr.: 0806H
Default: 1 Related Section: N/A
Applicable Control Mode: P/S/T
Unit: bps
Range: 0 ~ 5
Settings:
0: Baud rate 4800 (data transmission speed: bits / second)
1: Baud rate 9600 (data transmission speed: bits / second)
2: Baud rate 19200 (data transmission speed: bits / second)
3: Baud rate 38400 (data transmission speed: bits / second)