CHAPTER 5: IP ADDRESSING SETTING PARAMETERS
MULTILINK ML1600 ETHERNET COMMUNICATIONS SWITCH – INSTRUCTION MANUAL 5–11
To set the SNTP server to be 3.94.210.5 (with a time out of 3 seconds and a number of
retries set to 3 times); allowing the synchronization to be ever 5 hours, the following
sequence of commands are used
ML1600# sntp
ML1600(sntp)##
setsntp server=3.94.210.5 timeout=3 retry=3
SNTP server is added to SNTP server
database
ML1600(sntp)## sync hour=5
ML1600(sntp)##
sntp enable
SNTP is already enabled.
ML1600(sntp)## exit
ML1600(sntp)#
SNTP parameters can be configured through the EnerVista Secure Web Management
software with the Configuration > SNTP menu item. The SNTP menu allows the time zone
(hours from GMT) to be defined along with other appropriate parameters on setting the
time and synchronizing clocks on network devices.