Hitachi L100 Power Supply User Manual


 
L100 Inverter
Troubleshooting
and Maintenance
6–3
Troubleshooting Tips
The table below lists typical symptoms and the corresponding solution(s).
Symptom/condition Probable Cause Solution
The motor
will not run.
The inverter
outputs U, V, W
are not supply-
ing voltage.
Is the frequency command source
A01 parameter setting correct?
Is the Run command source A02
parameter setting correct?
Make sure the parameter
setting A01 is correct.
Make sure the parameter
setting A02 is correct.
Is power being supplied to termi-
nals L1, L2, and L3(N)? If so, the
POWER lamp should be on.
Check terminals L1, L2, and
L3(N), then U/T1, V/T2,
and W/T3.
Turn on the power supply or
check fuses.
Is there an error code
EXX
displayed?
Press the Func. key and
determine the error type.
Then clear the error (Reset).
Are the signals to the intelligent
input terminals correct?
Is the Run Command active?
Is the [FW] terminal (or [RV])
connected to P24 (via switch, etc.)
Verify the terminal functions
for C01 - C05 are correct.
Turn on Run Command.
Supply 24V to [FW] or [RV]
terminal, if configured.
Has the frequency setting for F01
been set greater than zero?
Are the control circuit terminals H,
O, and L connected to the potenti-
ometer?
Set the parameter for F01 to
a safe, non-zero value.
If the potentiometer is the
frequency setting source,
verify voltage at “O” > 0V.
Is the RS (reset) function or FRS
(free-run stop) function on?
Turn off the command(s).
Inverter outputs
U, V, W are
supplying
voltage.
Is the motor load too heavy?
Reduce load, and test the
motor independently.
The optional
remote operator
is used (DR/W)
Are the operational settings
between the remote operator and
the inverter unit correct?
Check switches 1 and 2 on
the optional remote operator
(copy unit).
The direction of the motor is
reversed.
Are the connections of output
terminals U/T1, V/T2, and W/T3
correct?
Is the phase sequence of the motor
forward or reverse with respect to
U/T1,V/T2, and W/T3?
Make connections according
to the phase sequence of the
motor. In general:
FWD = U-V-W, and
REV=U-W-V.
Are the control terminals [FW] and
[RV] wired correctly?
Is parameter F04 properly set?
Use terminal [FW] for
forward, and [RV] is reverse.
Set motor direction in F04.