Hitachi L100 Power Supply User Manual


 
“C” Group: Intelligent Terminal Functions
Configuring
Drive Parameters
3–32
The output logic convention is programmable for terminals 11 and 12. The open-collec-
tor output terminals 11 and 12 default to normally open (active low), but you can select
normally closed (active high) for terminals 11 and 12 in order to invert the sense of the
logic.
Summary Table - this table shows all six functions for the logical outputs (11, 12) at a
glance. Detailed descriptions of these functions, related parameters and settings, and
example wiring diagrams are in Chapter 4, starting on page 4–18.
“C” Function
Run-
time
Edit
Defaults DOP,DRW,DOP+
Func.
Code
Name Description
EU/
US
Units
Func.
Code
Name
C31 Terminal 11 active
state
Select logic convention, two
option codes:
00...normally open [NO]
01...normally closed [NC]
00 F-35 OUT-TM
O/C-1
C32 Terminal 12 active
state
Select logic convention, two
option codes:
00...normally open [NO]
01...normally closed [NC]
00 F-35 OUT-TM
O/C-2
C33 Alarm relay active
state
Select logic convention, two
option codes:
00...normally open [NO]
01...normally closed [NC]
01 F-35 OUT-TM
O/C-RY
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
00 RUN Run signal ON when inverter is in Run Mode
OFF when inverter is in Stop Mode
01 FA1 Frequency arrival
type 1 signal
ON when output to motor is at the set frequency
OFF when output to motor is off, or in any accelera-
tion or deceleration ramp
02 FA2 Frequency arrival
type 2 signal
ON when output to motor is at or above the set
frequency, even if in accel. or decel. ramps
OFF when output to motor is off, or at a level below
the set frequency
03 OL Overload advance
notice signal
ON when output current is more than the set thresh-
old for the overload signal
OFF when output current is less than the set threshold
for the overload signal
04 OD Output deviation for
PID control
ON when PID error is more than the set threshold for
the deviation signal
OFF when PID error is less than the set threshold for
the deviation signal