Hitachi L100 Power Supply User Manual


 
L100 Inverter
Appendix B
B–5
Fine Tuning Functions
“B” Group Parameters Default Setting
User Setting
Func. Code Name -FE (Europe) -FU (USA)
B01 Selection of restart mode 00 00
B02 Allowable under-voltage power
failure time
1.0 1.0
B03 Delay before motor restart time 1.0 1.0
B12 Level of electronic thermal setting Rated current
for each
inverter
Rated current
for each
inverter
B13 Electronic thermal characteristic 01 01
B21 Overload restriction operation mode 01 01
B22 Overload restriction setting Rated current
x 1.25
Rated current
x 1.25
B23 Deceleration rate at overload restric-
tion
1.0 1.0
B31 Software lock mode selection 01 01
B32 Reactive current setting Rated current
x 0.58
Rated current
x 0.58
B81 Analog frequency meter adjustment 80 80
B82 Start frequency adjustment 0.5 0.5
B83 Carrier frequency setting 5.0 5.0
B84 Initialization mode (parameters or
trip history)
00 00
B85 Country code for initialization 01 02
B86 Frequency scalar conversion factor 1.0 1.0
B87 STOP key enable 00 00
B88 Resume on FRS cancellation mode 00 00
B89 Data select for digital op. OPE-J 01 01
Technologies Inc.
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com