“B” Group: Fine Tuning Functions
Configuring
Drive Parameters
3–26
B82 Start frequency
adjustment
Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
✘ 0.5 Hz F-02 FMIN.
B83 Carrier frequency
setting
Sets the PWM carrier (internal
switching frequency), range is
0.5 to 16.0 kHz
✘ 5 kHz F-36 CARRIER
B84 Initialization mode
(parameters or trip
history)
Select the type of initialization
to occur, two option codes:
00...Trip history clear
01...Parameter initialization
✘ 00 — F-38 INIT
MODE
B85 Country code for
initialization
Select default parameter values
for country on initialization,
four options, option codes:
00...Japan version
01...Europe version
02...US version
03...reserved (do not set)
✘ 01/02 — F-38 INIT SEL
B86 Frequency scalar
conversion factor
Specify a constant to scale the
displayed frequency for D07
monitor, range is 0.1 to 99.9
✘ 1.0 — Mon. /HZ
B87 STOP key enable Select whether the STOP key
on the keypad is enabled, two
option codes:
00...enabled
01...disabled
✘ 00 — F-28 STOP-SW
B88 Resume on FRS
cancellation mode
Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00...Restart from 0Hz
01...Restart from frequency
detected from real speed of
motor
✘ 00 — F-10 RUN FRS
B89 Data select for digital
operator OPE-J
Select the monitoring data to
send to the hand-held digital
operator, seven option codes:
01...Output frequency (D01)
02...Output current (D02)
03...Motor direction (D03)
04...PID PV feedback (D04)
05...Input states for input
terminals (D05)
06...Output states for output
terminals (D06)
07...Scaled output frequency
(D07)
✔ 01 — Mon. PANEL
“B” Function
Run-
time
Edit
Defaults DOP,DRW,DOP+
Func.
Code
Name Description
EU/
US
Units
Func.
Code
Name
Technologies Inc.