Hitachi L100 Power Supply User Manual


 
L100 Inverter
Operations
and Monitoring
4–7
Multi-Speed Select
The inverter provides storage parameters for up to
16 different target frequencies (speeds) that the
motor output uses for steady-state run condition.
These speeds are accessible through programming
four of the intelligent terminals as binary-encoded
inputs CF1 to CF4 per the table below. These can
be any of the five inputs, and in any order. You can
use fewer inputs if you need eight or less speeds.
Note: When choosing a subset of speeds to use,
always start at the top of the table, and with the
least-significant bit: CF1, CF2, etc.
The figure below shows how input switches config-
ured with CF1 functions can change the motor
speed in real time.
.
NOTE: Speed 1 is set by the A01
parameter value.
Multi-
speed
Input Function
CF4 CF3 CF2 CF1
Speed 1 0000
Speed 2 0001
Speed 3 0010
Speed 4 0011
Speed 5 0100
Speed 6 0101
Speed 7 0110
Speed 8 0111
Speed 9 1000
Speed 101001
Speed 111010
Speed 121011
Speed 131100
Speed 141101
Speed 151110
Speed 161111
1st
time
CF1
CF2
CF3
2nd
3rd
7th
6th
5th
4th
8th
Speed
Switches
Fwd Run
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
02 CF1 Multi-speed select,
Bit 0 (LSB)
ON Binary encoded speed select, Bit 0, logical 1
OFF Binary encoded speed select, Bit 0, logical 0
03 CF2 Multi-speed select,
Bit 1
ON Binary encoded speed select, Bit 1, logical 1
OFF Binary encoded speed select, Bit 1, logical 0
04 CF3 Multi-speed select,
Bit 2
ON Binary encoded speed select, Bit 2, logical 1
OFF Binary encoded speed select, Bit 2, logical 0
05 CF4 Multi-speed select,
Bit 3 (MSB)
ON Binary encoded speed select, Bit 3, logical 1
OFF Binary encoded speed select, Bit 3, logical 0