Infortrend A16E-G2130-4 Power Supply User Manual


 
Chapter 5: Subsystem Maintenance and Upgrading
Step 7. Reinstall the controller module. After the DIMM module has been
properly installed, install the RAID controller. To do this, align the
controller module with the controller module bay. Then gently push
the controller module in the controller bay. Carefully push the
controller until you feel the contact when the board edge connectors
are being mated to the backplane. Do not use force. If unusual contact
resistance is felt, try it again. Use the ejection levers on the sides of
the controller to secure it into the chassis.
When the controller is inserted with the lever at its the lowest position,
notches on the levers should properly clinch to the round metal
protrusions on the interior walls of module bay. You may then pull the
lever upward to secure the controller into module bay.
Step 8. Next secure the controller module into the subsystem by fastening the
screws through holes underneath each ejection lever.
5.4. Replacing a Faulty BBU
The BBU is an optional item for the subsystem that can sustain cache memory in the
event of a power failure or in the unlikely event of failing both PSUs. The BBU provides
additional data security and helps minimize the chance of losing data due to power
outages.
A BBU consists of a metal bracket, battery cell pack, and a PCB board that connects to
the controller module. Each BBU is secured to the subsystem using retention screws.
Please read the BBU handling precautions below before proceeding with the replacement
procedure.
Fault Conditions:
A BBU failure can result from the following:
1. A BBU has lost its ability to hold electrical charge. This may be the case after the
battery cells have been recharged for many times regardless of how long the module
has been used. Therefore, a stable power source is important for system operation.
2. The charger circuitry implemented with the controller has failed.
There are other conditions that might trigger the BBU fault events and trigger the BBU
fault LED:
1. The temperature sensor embedded with the subsystem’s charger circuit reports a
temperature reading exceeding the preset threshold. The charger circuits will enter a
low-power and self-protection state.
Replacing a Faulty BBU 5-9